COMMISSIONING
Part No.: 4417340 Revision 1 Service Manual 229
954 SmartServo FlexLine
Name Value Range Default Value Description
[Analog output
safety function
status]
(RO)
Status:
< H >, < O >, < U >, < W >
Status Code:
Defined in Section 7.3.13.1
Status:
< H >
Status Code:
NO ERROR
H: Healthy
O: Overfill condition
U: Underfill condition
W: Warning condition, safe state
is active, or proof test is overdue
(status is NO ERROR).
[Analog output
safety
shutdown
counter]
(RO)
< 0 – 3.402823 × 10
38
> < 0 > The number of safe state
activations that have occurred
for the analog output.
[Analog output
safety
shutdown
reason]
(RO)
Safety Function Status
Code
NO ERROR The safety function status code
identifying the reason for the last
time an analog output safe state
activation occurred.
[Analog output
start overfill
proof test]
Command Initiates an analog output overfill
proof test if an actual analog
output safe state is not currently
active. Upon activation, a
simulated overfill condition will
occur. An active poof test will
terminate if an actual analog
output safe state is activated, or
if the analog output proof test
timeout value is exceeded.
[Analog output
start underfill
proof test]
Command Initiates an analog output
underfill proof test if an actual
analog output safe state is not
currently active. Upon
activation, a simulated underfill
condition will occur. An active
poof test will terminate if an
actual analog output safe state
is activated, or if the analog
output proof test timeout value is
exceeded.