COMMISSIONING 
 
Part No.: 4417340 Revision 1  Service Manual    229 
  954 SmartServo FlexLine 
Name  Value Range  Default Value  Description 
[Analog output 
safety function 
status] 
(RO) 
Status: 
< H >, < O >, < U >, < W > 
Status Code: 
Defined in Section 7.3.13.1 
Status: 
< H > 
Status Code: 
NO ERROR 
H: Healthy 
O: Overfill condition 
U: Underfill condition 
W: Warning condition, safe state 
is active, or proof test is overdue 
(status is NO ERROR). 
[Analog output 
safety 
shutdown 
counter] 
(RO) 
< 0 – 3.402823 × 10
38
 >  < 0 >  The number of safe state 
activations that have occurred 
for the analog output. 
[Analog output 
safety 
shutdown 
reason] 
(RO) 
Safety Function Status 
Code 
NO ERROR  The safety function status code 
identifying the reason for the last 
time an analog output safe state 
activation occurred. 
[Analog output 
start overfill 
proof test] 
Command    Initiates an analog output overfill 
proof test if an actual analog 
output safe state is not currently 
active.  Upon activation, a 
simulated overfill condition will 
occur. An active poof test will 
terminate if an actual analog 
output safe state is activated, or 
if the analog output proof test 
timeout value is exceeded. 
[Analog output 
start underfill 
proof test] 
Command    Initiates an analog output 
underfill proof test if an actual 
analog output safe state is not 
currently active.  Upon 
activation, a simulated underfill 
condition will occur. An active 
poof test will terminate if an 
actual analog output safe state 
is activated, or if the analog 
output proof test timeout value is 
exceeded.