COMMISSIONING 
 
Part No.: 4417340 Revision 1  Service Manual    69 
  954 SmartServo FlexLine 
Name  Value Range  Default Value  Explanation 
[Primary value gain]    <1.0> 
The calculated primary 
value can be multiplied with 
a desired gain. 
[Primary value offset]    <0.0> 
The calculated primary 
value can be given an offset.
[Secondary value]   
 
 
Shows the measured 
product level as an ullage 
value with the same fields 
as explained at the primary 
value. 
[High high alarm] 
[High alarm] 
[Low alarm] 
[Low low alarm] 
[Alarm hysteresis] 
 All <1E+22> 
Sets the respectively alarm 
threshold for the primary 
value, taking in account the 
hysteresis. 
[Alarm test enable]  <Enable> 
<Disable> 
<Disable> 
When enabled, during one 
minute there will be a 
simulated alarm, determined 
by entity [Alarm test], by 
putting the primary at the 
[Alarm test] threshold plus or 
minus 1/8 inch. 
[Alarm test]  <No alarm> 
<High alarm> 
<High high alarm> 
<Low alarm> 
<Low low alarm> 
<No alarm> 
Determines which alarm test 
threshold will be simulated 
[Kill measurement]     
With this command the 
actual measured primary 
value can be undone 
(killed). The purpose is then 
to overwrite this measured 
value. 
[Manual overwrite]     
The desired overwritten 
primary value (If killed). 
[Resurrect]    
With this command the 
manual overwritten value 
will be undone, and the 
Primary value shows it 
normal measured value. 
[Manual overwrite status]     
Shows the actual manual 
overwrite status. (Active or 
inactive) 
[Operational status]     
Shows the actual 
operational status. (I1, I2, I3 
or DM)