Figure 6-6 Adding access permissions
You can authorize and delete access users in batches.
5. Click OK to complete the task of adding access management settings.
6. On the Authorization Operations tab page, click Synchronize to Device,
select the
modied access control devices, and click Start Synchronization.
Figure 6-7 Synchronizing access permissions
7. When Synchronization Status is Synchronization completed for the related
devices, close the Synchronize Access Permission page.
Step 2 Set an alarm for card readers.
Set Logical level
conguration for reader removed based on the ngerprint
reader congured for the access control system.
● If the access control system uses a Card and password reader, choose
Monitoring > Aisle > Access Actuator Group > Access Actuator n on the
ECC800-Pro WebUI, click Running Parameters, and set Logical level
conguration for reader removed of the corresponding card reader to High
level alarm.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 6 Feature Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 139