EasyManua.ls Logo

Huawei ECC800-Pro - Page 95

Huawei ECC800-Pro
368 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pin De
nitio
n
Signal
Description
Status Description Initial
Status
Descriptio
n
3 DRV Controls
battery
circuit
breaker trip
and outputs
12 V driving
signals
0 V: There is no
driving signal for
BCB tripping.
12 V: There is a
driving signal for
BCB tripping.
0V
4 GND Secondary
side ground
Table 3-80 BCB_IN and BCB_OUT cascading port pin denitions
Pin De
nitio
n
BCB_IN
Signal
Descriptio
n
BCB_OUT
Signal
Description
Status
Description
Initial
Status
Descripti
on
1 OL Species
whether
the BCB
connects
to the
signal
output
port.
Species
whether the
cascaded
BCBs
connect to
the signal
input port.
Grounded:
BCB
connected.
Disconnect
ed: BCB
not
connected.
Disconne
cted
Receives
BCB
comman
ds sent
by the
UPS and
supports
BCB port
cascadin
g
manage
ment.
2 STA Signal
output
port for
the battery
circuit
breaker
status
Monitors
whether the
cascaded
BCBs are
connected
to the input.
Grounded:
The
battery
circuit
breaker is
ON.
Disconnect
ed: The
battery
circuit
breaker is
OFF.
Disconne
cted
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 3 Device Description