29 - 16
29.4  Preparatory Procedure for Accessing
29.4.4  Accessing the PLC by the GX Developer
2 When connecting the GOT and PC with USB
(1) When the Q/QnA/ACPU, motion controller CPU (A Series) is connected
The following is an access example by GX Developer (When connected to the A Series) when the 
GOT and PC are connected by USB.
1 Click [Online]   [Read from PLC] in GX 
Developer.
2 Set the [PLC Series] to [ACPU].
3 The [Connection Setup] is displayed.
4 Set the [Connection Setup]:
PC side I/F : Serial
PLC side I/F : PLC module
Other station : No specification
5 Double-click [PLC module] of the PLC 
side I/F to display [PLC side IF Detailed 
setting of PLC module].
6 Check-mark either of the following in 
[PLC side IF Detailed setting of PLC 
module].
[via GOT (Bus) transparent mode]
[via GOT (direct coupled) transparent 
mode]
7 Return to [Transfer Setup] and double-
click [Serial] of the PC side I/F to display 
[PC side I/F Serial setting].
8 Select [USB] in [PC side I/F Serial 
setting].
9 The screen returns to the [Connection 
Setup]. Click the   to check 
if GX Developer has been connected to 
the ACPU.
Bus connection
Direct CPU connection
connection test