15 - 22
15.3 Preparatory Procedure for Monitoring
15.3.3 Setting communication interface (Communication settings)
2 Communication detail settings
Item Description Range
Transmission Speed
Set this item when change the transmission speed used for com-
munication with the connected equipment.
<Default: 19200bps>
4800bps, 9600bps, 19200bps,
38400bps, 57600bps
Startup Time
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
<Default: 3 seconds>
3 to 30 seconds
Host Address
Specify the host address (station No. of the PLC to which the GOT
is connected) in the network of the GOT.
<Default: 1>
1 to 31
Delay Time
Set this item to adjust the transmission timing of the communica-
tion request from the GOT.
<Default: 0 ms>
0 to 30 ( 10 ms)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GOT1000 Series and is the answer not in the manual?

Mitsubishi GOT1000 Series Specifications

General IconGeneral
Power Supply24 VDC
TypeHMI (Human Machine Interface)
SeriesGOT1000
Resolution640 x 480 pixels
Touch Panel TypeResistive
InterfaceRS-232, USB
Storage Temperature-20 to 60°C
Protection RatingIP65
Display TypeTFT LCD
Brightness400 cd/m²
Backlight Life50, 000 hours
CPURISC
Shock Resistance147 m/s²
Display Size10.4 inches