23.5 Precautions
1 Precautions of connection to the inverter
(1) Make sure to establish inverter system with No.0 station.
(2) Up to 10 inverters can be connected.
(3) Do not make any change for each communication parameter of the inverter side from GOT. If
changed, the communication to the inverter cannot be made.
(4) When setting “8888” or “9999” to the parameter (Pr) of the inverter
“8888” and “9999” are numerical values which have special roles. When specifying from the GOT, it
will be as follows.
(5) Make sure to use GD for screen switching and system information devices.
(6) Since the inverter does not have a clock function, the settings of “time adjusting” or “time broad
cast” by GOT clock control will be disabled.
Set value of inverter side Value specified by GOT
8888 65520
9999 65535