EasyManua.ls Logo

Mitsubishi GOT1000 Series - Page 973

Mitsubishi GOT1000 Series
1216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23.5 Precautions
23 - 31
17
CONNECTION TO
ALLEN-BRADLEY PLC
18
CONNECTION TO
SIEMENS PLC
19
MICROCOMPUTER
CONNECTION
20
CONNECTION TO OMRON
TEMPERATURE
CONTROLLER
21
CONNECTION TO
YAMATAKE TEMPERATURE
CONTROLLER
22
CONNECTION TO RKC
TEMPERATURE
CONTROLLER
23
CONNECTION TO
FREQROL SERIES
INVERTER
24
SERVO AMPLIFIER
CONNECTION
23.5 Precautions
1 Precautions of connection to the inverter
(1) Make sure to establish inverter system with No.0 station.
(2) Up to 10 inverters can be connected.
(3) Do not make any change for each communication parameter of the inverter side from GOT. If
changed, the communication to the inverter cannot be made.
(4) When setting “8888” or “9999” to the parameter (Pr) of the inverter
“8888” and “9999” are numerical values which have special roles. When specifying from the GOT, it
will be as follows.
(5) Make sure to use GD for screen switching and system information devices.
(6) Since the inverter does not have a clock function, the settings of “time adjusting” or “time broad
cast” by GOT clock control will be disabled.
Set value of inverter side Value specified by GOT
8888 65520
9999 65535

Table of Contents

Related product manuals