Because RFL™ and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specifications without notice.
RFL DS-562I RFL Electronics Inc.
June 14, 2007 6 (973) 334-3100
12. On the DS-562I check the setting of DIP switch SW1-1 through SW1-5.
SW1-1 through SW1-5 controls the modules transmit and receive timeslot. Set the
switches to achieve the desired timeslot setting as shown in Table 8.
13. On the DS-562I check the setting of DIP switch SW2-1 through SW2-6.
SW2-1 through SW2-6 controls the modules transmit address. Set the switches to
achieve the desired transmit address setting as shown in Table 9.
14. On the DS-562I check the setting of DIP switch SW3-1 through SW3-6.
SW3-1 through SW3-6 controls the modules receive address. Set the switches to
achieve the desired receive address setting as shown in Table 9.
15. On the DS-562I check the setting of DIP switch SW4-1.
SW4-1 turns the octet timing on or off. Right turns the service off, left turns the octet
timing on. Set the switch to the desired position.
16. On the DS-562I check the setting of DIP switch SW4-2.
SW4-2 selects normal or inverted receive clock. Right sets normal polarity, left sets
inverted polarity. If the DS-562I does not reliably receive data from the 64/56 Kbps
connector, the receive clock may have to be inverted. For the initial setup, set the
switch to the right.
17. On the DS-562I check the setting of DIP switch SW4-3.
SW4-3 selects normal or inverted transmit clock. Right sets normal polarity, left sets
inverted polarity. If the user equipment does reliably receive data from the DS-
562I’s 64/56 Kbps connector, the transmit clock may have to be inverted. For the
initial setup, set the switch to the right.
18. On the DS-562I check the setting of DIP switch SW4-4.
SW4-4 turns the squelch on or off. Right turns the squelch off, left turns the squelch
on (the DS-562I stops sending data out the 64/56 Kbps connector upon loss of valid
receive address). Set the switch to the desired setting.
19. On the DS-562I check the setting of DIP switch SW4-7.
SW4-7 sets the data rate. Right selects 64 Kbps, left selects 56 Kbps. Set the switch
to the desired setting.
20. On the DS-562I check the setting of DIP switch SW4-8.
SW4-8 selects the DS-562I transmit bus direction. Right selects transmit on B,
receive on A (for drop and insert B), left selects transmit of A, receive on B (drop and
insert A or terminal end). Set the switch to the desired setting.
21. On the DS-562I check the setting of DIP switch SW5-1.
SW5-1 selects T1/E1. Right selects T1 carrier, left selects E1 carrier. Set the switch
for the format being used.