Because RFL™ and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specifications without notice.
Table 15. Analog channel 1, 2, 3 & 4 input offset magnitudes for TMX
Offset setting in binary
Decimal
Equivalent
Of setting
Multiplier Offset
Magnitude
In mV
(1,2)
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
0 0 0 0 0 0 0 0 0 x 40 mV 0
0 0 0 0 0 0 0 1 1 x 40 mV 40
0 0 0 0 0 0 1 0 2 x 40 mV 80
0 0 0 0 0 0 1 1 3 x 40 mV 120
0 0 0 0 0 1 0 0 4 x 40 mV 160
0 0 0 0 0 1 0 1 5 x 40 mV 200
1 1 1 1 1 0 1 0 250 x 40 mV 10,000
1 1 1 1 1 0 1 1 251 x 40 mV 10,040
1 1 1 1 1 1 0 0 252 x 40 mV 10,080
1 1 1 1 1 1 0 1 253 x 40 mV 10,120
1 1 1 1 1 1 1 0 254 x 40 mV 10,160
1 1 1 1 1 1 1 1 255 x 40 mV 10,200
Table 16. Analog channel 1, 2, 3 & 4 output offset magnitudes for TMR
Offset setting in binary
Decimal
Equivalent
Of setting
Multiplier Offset
Magnitude
In mA
(1,2)
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
0 0 0 0 0 0 0 0 0
x 200 μA
0
0 0 0 0 0 0 0 1 1
x 200 μA
0.2
0 0 0 0 0 0 1 0 2
x 200 μA
0.4
0 0 0 0 0 0 1 1 3
x 200 μA
0.6
0 0 0 0 0 1 0 0 4
x 200 μA
0.8
0 0 0 0 0 1 0 1 5
x 200 μA
1.0
1 1 1 1 1 0 1 0 250
x 200 μA
50.0
1 1 1 1 1 0 1 1 251
x 200 μA
50.2
1 1 1 1 1 1 0 0 252
x 200 μA
50.4
1 1 1 1 1 1 0 1 253
x 200 μA
50.6
1 1 1 1 1 1 1 0 254
x 200 μA
50.8
1 1 1 1 1 1 1 1 255
x 200 μA
51.0
Notes for Tables 15 and 16:
1.
In the TMX, the offset value (magnitude and polarity) will be subtracted from the data generated by the A/D
converter. The input offset magnitude setting equals the number of 40mV increments.
2.
In the TMR, the offset value (magnitude and polarity) will be added to the data sent to the D/A converter.
The output offset magnitude setting equals the number of 200 μA increm
ents.
RFL TMX
/TMR RFL Electronics Inc.
January
25, 2012 31 (973) 334-3100