EasyManua.ls Logo

Siemens SINAMICS G120 - Page 182

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring the fieldbus
7.6 Communication via RS485
Inverter with CU230P-2 Control Units
182 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Multi-State Input Objects
Instance
ID
Object name
Description
Possible values
Access type
Parameter
MSI0
FAULT_1
Fault number 1
See List Manual "List of faults and
alarms"
R
r0947[0]
MSI1
FAULT_2
Fault number 2
R
r0947[1]
MSI2
FAULT_3
Fault number 3
R
r0947[2]
MSI3
FAULT_4
Fault number 4
R
r0947[3]
MSI4
FAULT_5
Fault number 5
R
r0947[4]
MSI5
FAULT_6
Fault number 6
R
r0947[5]
MSI6
FAULT_7
Fault number 7
R
r0947[6]
MSI7
FAULT_8
Fault number 8
R
r0947[7]
MSI8
WARNING_1
Warning number 1
R
r2110[0]
MS9
WARNING_2
Warning number 2
R
r2110[1]
MSI10
WARNING_3
Warning number 3
R
r2110[2]
MSI11
WARNING_4
Warning number 4
R
r2110[3]
MSI12
WARNING_5
Warning number 5
R
r2110[4]
MSI13
WARNING_6
Warning number 6
R
r2110[5]
MSI14
WARNING_7
Warning number 7
R
r2110[6]
MSI15
WARNING_8
Warning number 8
R
r2110[7]

Table of Contents