Configuring the fieldbus
7.7 Communication over CANopen
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
209
2 Device profile or
manufacturer-specific
p8609.1 SDO U32 1 rw
1200 1st server SDO
parameter
1 COB ID client -> server
r8610.0 SDO U32 – r
2 COB ID server -> client
r8610.1 SDO U32 – r
RPDO configuration objects
The following tables list the communication and mapping parameters together with the
indexes for the individual RPDO configuration objects. The configuration objects are
established via SDO. The "SINAMICS parameters" column shows the parameter numbers
assigned in the converter.
Table 7- 27 RPDO configuration objects - communication parameters
Predefined
connection set
Receive PDO 1 communication parameter
Largest subindex supported
Receive PDO 2 communication parameter
Largest subindex supported