Setting functions
8.2 Inverter control
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
237
Advanced settings
To change the number of command data sets in STARTER, you must open your STARTER
project offline.
Figure 8-10 Editing command data sets in STARTER
You can edit command data sets if, in the STARTER project tree, you select
"Configuration".
If you require more than two command data sets, then add command data sets using
this button or remove them.
,
To simplify commissioning
several command data sets, under the "Command data
sets" tab there is a copy function.
Parameter
Description
p0010 = 15
Drive commissioning: Data sets
p0170
Number of command data sets
(factory setting: 2)
p0170 = 2, 3 or 4
p0010 = 0
Drive commissioning: Ready
r0050
Displaying the number of the CDS that is currently active
p0809[0]
Number of the command data set to be copied (source)
p0809[1]
Number of the command data set to which the data is to be copied (target)
p0809[2] = 1
Copying is started
Once copying has been completed, the inverter sets p0809[2] to 0.
p0810
Command data set selection CDS bit 0
p0811
Command data set selection CDS bit 1
r0050
Displaying the number of the CDS that is currently active