Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
388 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Table 12- 18 PM230, IP55, Frame Sizes E, 3 AC 380 V … 480 V
Order No. - Filtered, Class A
Order No. - Filtered, Class B
Rated / LO power
Rated / LO input current
Rated / LO Output current
37 kW
70 A
45 kW
84 A
HO power
HO input current
30 kW
56 A
37 kW
70 A
Fuse according to IEC
3NA3830
3NA3832
Required cooling air flow
Cross section of line and motor cable 25 … 50 mm
2
25 … 50 mm
2
Tightening torque for line and motor cable
Table 12- 19 PM230, IP55, Frame Sizes F, 3 AC 380 V … 480 V
Order No. - Filtered, Class A
Order No. - Filtered, Class B
Rated / LO power
Rated / LO input current
Rated / LO Output current
55 kW
102 A
110 A
75 kW
135 A
145 A
90 kW
166 A
178 A
HO power
HO input current
45 kW
84 A
55 kW
102 A
75 kW
135 A
Fuse according to IEC
3NA3836
3NA3140
3NA3144
Required cooling air flow
Cross section of line and motor cable 35 … 120 mm
2
35 … 120 mm
2
35 … 120 mm
2
Tightening torque for line and motor cable