Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
393
Table 12- 24 PM240, IP20, frame sizes D, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
Rated/LO power
Rated/LO input current
18.5 kW
46 A
22 kW
53 A
30 kW
72 A
HO power
HO input current
15 kW
40 A
18.5 kW
46 A
22 kW
56 A
Fuse according to UL (from SIEMENS)
Fuse according to UL (Class J)
3NE1817-0
3NE1818-0
3NE1820-0
Power loss 0.44 kW
0.55 kW
0.72 kW
Required cooling air flow
Cross section of line and motor cables 10 … 35 mm
2
10 … 35 mm
2
16 … 35 mm
2
Tightening torque for line and motor cables
Weight without filter
13 kg
13 kg
13 kg
Table 12- 25 PM240, IP20, frame sizes E, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
Rated/LO power
Rated/LO input current
Rated/LO output current
37 kW
88 A
75 A
45 kW
105 A
90 A
HO power
HO input current
30 kW
73 A
37 kW
90 A
Fuse according to UL (from SIEMENS)
3NE1021-0
3NE1022-0
Power losses without filter
0.99 kW
1.2 kW
Required cooling air flow
Cross section of line and motor cables 25 … 35 mm
2
25 … 35 mm
2
Tightening torque for line and motor cables
Weight without filter
16 kg