Installing
4.3 Installing Power Modules
Inverter with CU230P-2 Control Units
50 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Table 4- 11 Dimensions and clearances for PM240-2 in through-hole technology, FSA … FSC
2)
2)
2)
With shield connection kit: FSA: +84 mm; FSB: +85 mm; FSC: +89 mm
You can mount the mounting frames without any lateral clearance. For tolerance reasons, we recommend a lateral
clearance of approx. 1 mm.
3)
Total depth of the inverter: See below.
Table 4- 12 Mounting materials for PM240-2 in through-hole technology
Total depth of the inverter
Power Modules frame sizes FSA … FSF
+
As a minimum, the inverter comprises a Power Module and
an
inserted Control Unit:
Overall depth of the inverter = depth of the Power Module +
60 mm (Control Unit)
+ ② + ③
Inverter with inserted operator panel:
Overall depth of the inverter = depth of the Power Module
+ 73 mm (Control Unit + Basic Operator Panel BOP-2)
Overall depth of the inverter = depth of the Power Module
+ 82 mm (Control Unit + Intelligent Operator Panel IOP)
+ ② + ③ + ④
Power Module (degree of protection IP20) on a base
component:
The overall inverter depth increases by the depth of the base
component.
Power Modules with power above 160 kW (FSGX/GX)
For Power Modules with power above 160 kW, the depth of the Power Module corresponds
to the overall depth of the inverter.