Installing
4.3 Installing Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
49
Dimensions and drilling patterns for Power Modules with through-hole technology
Mounting cutout in the control cabinet for the PM230 and PM240-2 Power Modules;
Holes for fastening the mounting frame
FSA, FSB
FSC
Table 4- 9 Dimensions and clearances for PM230 in through-hole technology, FSA … FSC
2)
2)
2)
With shield connection kit: FSA: +84 mm; FSB: +85 mm; FSC: +89 mm
You can mount the mounting frames without any lateral clearance. For tolerance reasons, we recommend a lateral
clearance of approx. 1 mm.
3)
Overall depth of the inverter: See below.
Table 4- 10 Mounting materials for PM230 in through-hole technology