EasyManua.ls Logo

Siemens SINAMICS G120 - Page 48

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing
4.3 Installing Power Modules
Inverter with CU230P-2 Control Units
48 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Table 4- 6 Mounting hardware for PM250
Frame size
Material
Tightening torque
FSC
M5 screws
2.5 Nm
FSD, FSE
M6 screws
6 Nm
FSF
M8 screws
13 Nm
Table 4- 7 Dimensions and clearances for the PM260
Frame size
Dimensions (mm)
Clearances (mm)
Height
1)
Width
Depth
3)
a
b
c
Top
Bottom
Lateral
FSD without filter
419
275
204
325
235
11
300
300
0
2)
FSD with filter
512
275
204
419
235
11
300
300
0
2)
FSF without filter
634
350
316
598
300
11
350
350
0
2)
FSF with filter
934
350
316
899
300
11
350
350
0
2)
1)
Additional height with shield connection kit: +123 mm
2)
You can mount the Power Modules without any lateral clearance. For tolerance reasons, we recommend a lateral
clearance of approx. 1 mm.
3)
Overall depth of the inverter: See below.
Table 4- 8 Mounting hardware for the PM260
Frame size
Material
Tightening torque
FSD
M6 screws
6 Nm
FSF
M8 screws
13 Nm
Dimensions and drilling patterns for the PM330 GX Power Module with IP20 degree of protection
Installation material:
M8 screws, 15 Nm tightening
torque
Clearances:
30 mm at the side and front
200 mm at the top and bottom

Table of Contents

Other manuals for Siemens SINAMICS G120