144 Description Of Specific Functions
V560 Series High Performance Closed-Loop Vector Inverter User Manual
pull in.
6: Equipment fault or alarm
When there is fault for exception of inverter and sending fault or warning signal, terminal will output effective
signal/relay will pull in.
7: Reverse running
When electric motor rotates reversely, the terminal will output the valid signal/relay will pull in.
8: Running command valid
When running instruction of inverter is valid, the terminal will output the valid signal/relay will operate.
9: Running at zero speed
When running instruction is valid but output frequency of inverter is at zero and there is current output,
terminal will output effective signal/relay will pull in.
10: Speed not at zero
When the speed of rotator of electric motor is not at zero (VC mode) or output frequency is not at zero (VF or
SVC mode), terminal will output the valid signal/relay will pull in.
11: Inverter undervoltage stop
When inverter is in under-voltage stop and reporting Fu.008, the terminal will output the valid signal/relay will
pull in.
12: Terminal control effective
When control command of frequency converter is given not on panel, terminal will output the valid
signal/relay will pull in.
14: Running at power generating status (braking)
When inverter is in regenerative braking running state, terminal will output the valid signal/relay will pull in.
19: Completion of current stage of multi-stage running (0.5s pulse)
After completion of current stage of multi-stage running, terminal will output the valid pulse signal with 0.5s
width/relay will disconnect after pulling in for 0.5s.
20: Multi-stage running completed (0.5s pulse)
After completion of one cycle of multi-stage speed running, terminal will output the valid impulse signal with
0.5s width/relay will disconnect after pulling in for 0.5s.
21: Multi-stage running completed (continuous level output)
After completion of one cycle of multi-stage speed running, terminal will output continuous valid signal/relay
will pull in.
22: Multi-stage running cycle completed (0.5s pulse)
After completion of one cycle of multi-stage speed running, terminal will output effective impulse signal with
0.5s width/relay will disconnect after pulling in for 0.5s.
23: Swing frequency upper and lower limit
After selection of wobbulation, if the frequency fluctuation range of wobbulation, which calculated based on
center frequency, is above upper limit frequency F0.1.21 or below lower limit frequency F0.1.22, then
terminal will output effective signal/relay will pull in.
24: Encoder direction
It is used to indicate the directional signal output by current encoder frequency division.
26/29/32: Monitoring parameters 1/2/3 below the lower limit