15.2  Alarm Displays
 15.2.2  Troubleshooting Alarms
15-21
A.400: 
Overvoltage 
(Detected in the 
main circuit 
power supply 
section of the 
SERVOPACK.)
The power supply 
voltage exceeded the 
specified range.
Measure the power 
supply voltage.
Set the AC/DC power 
supply voltage within the 
specified range.
–
The power supply is 
not stable or was 
influenced by a light-
ning surge.
Measure the power 
supply voltage.
Improve the power sup-
ply conditions, install a 
surge absorber, and then 
turn the power supply 
OFF and ON again. If an 
alarm still occurs, the 
SERVOPACK may be 
faulty. Replace the SER-
VOPACK.
–
The voltage for AC 
power supply was too 
high during accelera-
tion or deceleration.
Check the power sup-
ply voltage and the 
speed and torque 
during operation.
Set the AC power supply 
voltage within the speci-
fied range.
–
The external regener-
ative resistance is too 
high for the operating 
conditions.
Check the operating 
conditions and the 
regenerative resistance.
Select a regenerative 
resistance value that is 
appropriate for the oper-
ating conditions and load.
*3
The moment of inertia 
ratio or mass ratio 
exceeded the allow-
able value.
Check to see if the 
moment of inertia ratio 
or mass ratio is within 
the allowable range.
Increase the deceleration 
time, or reduce the load.
–
A failure occurred in 
the SERVOPACK.
–
While the main circuit 
power supply is OFF, turn 
the control power supply 
to the SERVOPACK OFF 
and ON again. If an alarm 
still occurs, the SERVO-
PACK may be faulty. 
Replace the SERVO-
PACK.
–
A.410: 
Undervoltage 
(Detected in the 
main circuit 
power supply 
section of the 
SERVOPACK.)
The power supply 
voltage went below 
the specified range.
Measure the power 
supply voltage.
Set the power supply volt-
age within the specified 
range.
–
The power supply 
voltage dropped 
during operation.
Measure the power 
supply voltage.
Increase the power supply 
capacity.
–
A momentary power 
interruption occurred.
Measure the power 
supply voltage.
If you have changed the 
setting of Pn509 (Momen-
tary Power Interruption 
Hold Time), decrease the 
setting.
page 6-11
The SERVOPACK 
fuse is blown out.
–
Replace the SERVO-
PACK and connect a 
reactor to the DC reactor 
terminals ( 1 and  2) on 
the SERVOPACK.
–
A failure occurred in 
the SERVOPACK.
–
The SERVOPACK may be 
faulty. Replace the SER-
VOPACK.
–
Continued on next page.
Continued from previous page.
Alarm Number: 
Alarm Name
Possible Cause Confirmation Correction Reference