15.2 Alarm Displays
15.2.7 Resetting Alarms Detected in Option Modules
15-50
2.
Select Display Alarm in the Menu Dialog Box.
The Alarm Display Dialog Box will be displayed.
3.
Click the Alarm History Tab .
4.
Click the Clear Button.
The alarm history will be cleared.
This concludes the procedure to reset the alarm history.
15.2.7
Resetting Alarms Detected in Option Modules
If any Option Modules are attached to the SERVOPACK, the SERVOPACK detects the pres-
ence and models of the connected Option Modules. If it finds any errors, it outputs alarms.
You can delete those alarms with this operation.
Preparations
Always check the following before you clear an alarm detected in an Option Module.
The parameters must not be write prohibited.
Applicable Tools
The following table lists the tools that you can use to reset Option Module configuration errors
and the applicable tool functions.
This operation is the only way to reset alarms for Option Modules. The alarms are not reset
when you reset other alarms or when you turn OFF the power supply to the SERVOPACK.
Always remove the cause of an alarm before you reset the alarm.
Tool Function Reference
Digital Operator Fn014
Σ
-7-Series Digital Operator Operating Manual
(Manual No.: SIEP S800001 33)
SigmaWin+
Setup
Reset Configuration Error of
Option Module
Operating Procedure
on page 15-51