15.3 Warning Displays
15.3.2 Troubleshooting Warnings
15-57
15
Maintenance
A.912:
Internal Tempera-
ture Warning 1
(Control Board Tem-
perature Error)
The surrounding
temperature is too
high.
Check the surrounding
temperature using a
thermostat. Or, check
the operating status
with the SERVOPACK
installation environ-
ment monitor.
Decrease the surrounding
temperature by improving
the SERVOPACK installa-
tion conditions.
page 3-7
An overload alarm
was reset by turn-
ing OFF the power
supply too many
times.
Check the alarm display
to see if there is an
overload alarm.
Change the method for
resetting the alarm.
There was an
excessive load or
operation was
performed that
exceeded the
regenerative pro-
cessing capacity.
Use the accumulated
load ratio to check the
load during operation,
and use the regenera-
tive load ratio to check
the regenerative pro-
cessing capacity.
Reconsider the load and
operating conditions.
The SERVOPACK
installation orien-
tation is not cor-
rect or there is
insufficient space
around the SER-
VOPACK.
Check the SERVO-
PACK installation con-
ditions.
Install the SERVOPACK
according to specifications.
page 3-4,
page 3-7
A failure occurred
in the SERVO-
PACK.
The SERVOPACK may be
faulty. Replace the SERVO-
PACK.
A.913:
Internal Tempera-
ture Warning 2
(Power Board Tem-
perature Error)
The surrounding
temperature is too
high.
Check the surrounding
temperature using a
thermostat. Or, check
the operating status
with the SERVOPACK
installation environ-
ment monitor.
Decrease the surrounding
temperature by improving
the SERVOPACK installa-
tion conditions.
page 3-7
An overload alarm
was reset by turn-
ing OFF the power
supply too many
times.
Check the alarm display
to see if there is an
overload alarm.
Change the method for
resetting the alarm.
There was an
excessive load or
operation was
performed that
exceeded the
regenerative pro-
cessing capacity.
Use the accumulated
load ratio to check the
load during operation,
and use the regenera-
tive load ratio to check
the regenerative pro-
cessing capacity.
Reconsider the load and
operating conditions.
The SERVOPACK
installation orien-
tation is not cor-
rect or there is
insufficient space
around the SER-
VOPACK.
Check the SERVO-
PACK installation con-
ditions.
Install the SERVOPACK
according to specifications.
page 3-4,
page 3-7
A failure occurred
in the SERVO-
PACK.
The SERVOPACK may be
faulty. Replace the SERVO-
PACK.
Continued on next page.
Continued from previous page.
Warning Number:
Warning Name
Possible Cause Confirmation Correction Reference