6.2 Communication with Other MP Series
6.2.2 When the MP2300S Acts as Slave (ladder program which uses a MSG-RCV function)
6-32
Parameter list setting for the message transmit function
An example of a parameter list setting when reading 100 words of data from MW00100 from the destination
using the connection with a connection number = 2 follows:
Note: IN: Input, OUT: Output, SYS: For system use
Table 6.7 Parameter List Setting Example (parameter list start address Param=DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT Remarks
DW00000
– PARAM00 OUT
Process result
DW00001
– PARAM01 OUT
Status
DW00002
00002 PARAM02 IN
Connection number = 2
DW00003
– PARAM03 IN
Option (Setting unnecessary)
DW00004
0009H PARAM04 IN
Function code = 09H (Reads a holding register)
DW00005
00100 PARAM05 IN
Data address = 100 (Starting from MW00100)
DW00006
00100 PARAM06 IN
Data size = 100 (100 words)
DW00007
00001 PARAM07 IN
Remote CPU number = 1
DW00008
00000 PARAM08 IN
Coil offset = 0 word
DW00009
00000 PARAM09 IN
Input relay offset = 0 word
DW00010
00000 PARAM10 IN
Input register offset = 0 word
DW00011
00000 PARAM11 IN
Holding register offset = 0 word
DW00012
– PARAM12 SYS
Reserved by the system. (Zero clear at startup)
DW00013
– PARAM13 SYS
Reserved by the system.
DW00014
– PARAM14 SYS
Reserved by the system.
DW00015
– PARAM15 SYS
Reserved by the system.
DW00016
– PARAM16 SYS
Reserved by the system.