6.4  Communication with PLC Manufactured by Mitsubishi Electric Corporation (MELSEC protocol)
6.4.1  When the MP2300S Acts as Slave (automatic receive function is used)
6-75
Built-in Ethernet Communications
6.4  Communication with PLC Manufactured by Mitsubishi Electric 
Corporation (MELSEC protocol)
In Ethernet communication between the MP2300S and MELSEC (Q, A series) general-purpose PLC manufactured by 
Mitsubishi Electric Corporation, the MELSEC protocol (A-compatible 1E frame) is used as a communication protocol.
Using the MELSEC protocol allows a master to read/write the slave register content.
This chapter explains communication when the MP2300S acts as a slave and a master respectively.
For using the MP2300S as a slave, we explain communication using the automatic receive function.
For using the MP2300S as a master, we explain communication using the I/O message communication function.
6.4.1  When the MP2300S Acts as Slave (automatic receive function is used)
This section explains how to carry out a fixed buffer communication with the BUFSND command (with procedure) of 
the MELSEC Q series using the MP2300S automatic receive function.
Fig. 6.12  Message Flow with the MELSEC Q Series when the Automatic Receive Function Is Used
MELSEC protocol
(fixed buffer communication, with procedure)
MP2300S
218IFA
MP
/
E
thernet
LINK
0
0
23
S
&%
&%
8
4.;
176
0V
;#5-#9#
6'56
4&;
#./
/6:
64:
470
'44
$#6
+2
59
59
10
10
%0()
+06
572
/10
5612
$#66'4;
M-I/II
'
'
6'56
+06
01
01
MELSEC Q series
BUFSND command
(ladder application)
Slave
Master
MP2300S
(Local station)
MELSEC Q series
(Remote station)
EthernetEthernet
Communication Protocol
Type
Connection Type
Data Code Type
MELSEC protocol
TCP / UDP
BIN / ASCII
Automatic receive function
(ladderless)