6.4 Communication with PLC Manufactured by Mitsubishi Electric Corporation (MELSEC protocol)
6.4.1 When the MP2300S Acts as Slave (automatic receive function is used)
6-76
Caution
Communication using the automatic receive function is 1:1 communication.
Also, when “Communication Protocol Type: MELSEC” is used in communication with the MELSEC Q series, the MELSEC Q
series (master) side can read/write the holding register of the MP2300S (slave) using fixed buffer communication.
However, when the MP2300S acts as a slave, you cannot use the inter-CPU or random access communication, because of the
MELSEC specifications.
In addition, use the message receive function (MSG-RCV) when communicating with multiple remote devices.
Setting Example
The following figure illustrates one example of writing the contents of the data register (D00201 to D00300) of
MELSEC Q series (master) into the MP2300S (slave) holding register (MW00000 to MW00099).
The particular setup procedure is explained in the subsequent pages.
MP
/
E
thernet
LINK
0
0
23
S
&%
&%
8
4.;
176
0V
;#5-#9#
6'56
4&;
#./
/6:
64:
470
'44
$#6
+2
59
59
10
10
%0()
+06
572
/10
5612
$#66'4;
M-I/II
'
'
6'56
+06
01
01
MW00000
MW00001
MW00099
D00201
D00202
D00300
MW00098 D00299
Data size
100W
Data size
100W
Slave
Master
MP2300S
(Local station)
MELSEC Q series
(Remote station)
EthernetEthernet
IP address: 192.168.001.001
IP address: 192.168.001.002
TCP
BIN
Communication Protocol
Type
Connection Type
Data Code Type
MELSEC protocol
Port number: 10001 Port number: 10001
MP2300S MELSEC Q series
(Remote station)
(Local station)
Holding register (M register) Data Register (D register)
Write