6.2 Communication with Other MP Series
6.2.3 When the MP2300S Acts as Master (I/O message communication function is used)
6-45
Built-in Ethernet Communications
Parameter list setting example for message receive function
An example of a parameter list setting when receiving messages from a transmit source using the connection with
connection numbers = 5 and 6 follows:
Note: IN: Input, OUT: Output, SYS: For system use
Note: IN: Input, OUT: Output, SYS: For system use
Table 6.10 Parameter List Setting Example 1 (parameter list start address Param = DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT Remarks
DW00000
PARAM00 OUT
Process result
DW00001
PARAM01 OUT
Status
DW00002
00005 PARAM02 IN
Connection number = 5 (For receiving read operation)
DW00003
PARAM03 OUT
Option
DW00004
PARAM04 OUT
Function code
DW00005
PARAM05 OUT
Data address
DW00006
PARAM06 OUT
Data size
DW00007
PARAM07 OUT
Remote CPU number
DW00008
00000 PARAM08 IN
Coil offset = 0 word
DW00009
00000 PARAM09 IN
Input relay offset = 0 word
DW00010
00000 PARAM10 IN
Input register offset = 0 word
DW00011
00000 PARAM11 IN
Holding register offset = 0 word
DW00012
00000 PARAM12 IN
Writable address lower limit = MW00000
DW00013
65534 PARAM13 IN
Writable address upper limit = MW65534
DW00014
PARAM14 SYS
Reserved by the system. (Zero clear at startup)
DW00015
PARAM15 SYS
Reserved by the system.
DW00016
PARAM16 SYS
Reserved by the system.
Table 6.11 Parameter List Setting Example 2 (parameter list start address Param = DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT Remarks
DW00000
PARAM00 OUT
Process result
DW00001
PARAM01 OUT
Status
DW00002
00006 PARAM02 IN
Connection number = 6 (For receiving write opera-
tion)
DW00003
PARAM03 OUT
Option
DW00004
PARAM04 OUT
Function code
DW00005
PARAM05 OUT
Data address
DW00006
PARAM06 OUT
Data size
DW00007
PARAM07 OUT
Remote CPU number
DW00008
00000 PARAM08 IN
Coil offset = 0 word
DW00009
00000 PARAM09 IN
Input relay offset = 0 word
DW00
010
00000 PARAM10 IN
Input
register offset = 0 word
DW00011
00000 PARAM11 IN
Holding register offset = 0 word
DW00012
00000 PARAM12 IN
Writable address lower limit = MW00000
DW00013
65534 PARAM13 IN
Writable address upper limit = MW65534
DW00014
PARAM14 SYS
Reserved by the system. (Zero clear at startup)
DW00015
PARAM15 SYS
Reserved by the system.
DW00016
PARAM16 SYS
Reserved by the system.