6.2 Communication with Other MP Series
6.2.3 When the MP2300S Acts as Master (I/O message communication function is used)
6-45
Built-in Ethernet Communications
Parameter list setting example for message receive function
An example of a parameter list setting when receiving messages from a transmit source using the connection with
connection numbers = 5 and 6 follows:
Note: IN: Input, OUT: Output, SYS: For system use
Note: IN: Input, OUT: Output, SYS: For system use
Table 6.10 Parameter List Setting Example 1 (parameter list start address Param = DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT Remarks
DW00000
– PARAM00 OUT
Process result
DW00001
– PARAM01 OUT
Status
DW00002
00005 PARAM02 IN
Connection number = 5 (For receiving read operation)
DW00003
– PARAM03 OUT
Option
DW00004
– PARAM04 OUT
Function code
DW00005
– PARAM05 OUT
Data address
DW00006
– PARAM06 OUT
Data size
DW00007
– PARAM07 OUT
Remote CPU number
DW00008
00000 PARAM08 IN
Coil offset = 0 word
DW00009
00000 PARAM09 IN
Input relay offset = 0 word
DW00010
00000 PARAM10 IN
Input register offset = 0 word
DW00011
00000 PARAM11 IN
Holding register offset = 0 word
DW00012
00000 PARAM12 IN
Writable address lower limit = MW00000
DW00013
65534 PARAM13 IN
Writable address upper limit = MW65534
DW00014
– PARAM14 SYS
Reserved by the system. (Zero clear at startup)
DW00015
– PARAM15 SYS
Reserved by the system.
DW00016
– PARAM16 SYS
Reserved by the system.
Table 6.11 Parameter List Setting Example 2 (parameter list start address Param = DA00000)
Register
Number
Setting
Value
Parameter
Number
IN/OUT Remarks
DW00000
– PARAM00 OUT
Process result
DW00001
– PARAM01 OUT
Status
DW00002
00006 PARAM02 IN
Connection number = 6 (For receiving write opera-
tion)
DW00003
– PARAM03 OUT
Option
DW00004
– PARAM04 OUT
Function code
DW00005
– PARAM05 OUT
Data address
DW00006
– PARAM06 OUT
Data size
DW00007
– PARAM07 OUT
Remote CPU number
DW00008
00000 PARAM08 IN
Coil offset = 0 word
DW00009
00000 PARAM09 IN
Input relay offset = 0 word
DW00
010
00000 PARAM10 IN
Input
register offset = 0 word
DW00011
00000 PARAM11 IN
Holding register offset = 0 word
DW00012
00000 PARAM12 IN
Writable address lower limit = MW00000
DW00013
65534 PARAM13 IN
Writable address upper limit = MW65534
DW00014
– PARAM14 SYS
Reserved by the system. (Zero clear at startup)
DW00015
– PARAM15 SYS
Reserved by the system.
DW00016
– PARAM16 SYS
Reserved by the system.