EasyManua.ls Logo

YASKAWA MP2300S - Page 391

YASKAWA MP2300S
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix G MSG-SND/MSG-RCV Functions (Ethernet)
G.1 Message Transmit Function (MSG-SND)
A-69
Appendices
( 7 ) Data Address (PARAM05)
Specify the start address of the data.
The address must be input in decimal or hexadecimal numbers.
Example: When the start address is MW01000, specify “1000 (decimal)” or “3E8H (hexadecimal).”
The valid range of usable function codes and data addresses may differ, depending on the device type and device range
of the MELSEC side.
The following table gives the valid ranges of data addresses when using MELSEC as a protocol.
Note: 1. The device range may differ according to the MELSEC sequencer even within the device range. For
more information, refer to the MELSEC manual.
2. The register number corresponding to MP2000 can be adjusted by the offset setting of the MSG-SND
function.
Table G.7 Valid Range of Data Addresses (MELSEC bit device)
Device
Device Range of
ACPU Common
Commands
Decimal/
Hexa-
decimal
Function Code
Valid Range of
Data Addresses
Corresponding Register
Number
X
X0000 to X07FF Hexadecimal
02H: Input relay
0 to 2047 MB000000 to MB00127F
Y
Y0000 to Y07FF Hexadecimal
01H/0FH: Coil
0 to 2047 MB000000 to MB00127F
M
M0000 to M2047 Decimal
01H/05H/0FH: Coil
2048 to 4095 MB001280 to MB00255F
M
M9000 to M9255 Decimal
01H/05H/0FH: Coil
4096 to 4351 MB002560 to MB00271F
B
B0000 to B03FF Hexadecimal
01H/05H/0FH: Coil
4352 to 5375 MB002720 to MB00335F
F
F0000 to F0255 Decimal
01H/05H/0FH: Coil
5376 to 631 MB003360 to MB00351F
TS
TS000 to TS255 Decimal
02H: Input relay
2048 to 2303 MB001280 to MB00143F
TC
TC000 to TC255 Decimal
02H: Input relay
2304 to 2559 MB001440 to MB00159F
CS
CS000 to CS255 Decimal
02H: Input relay
2560 to 2815 MB001660 to MB00175F
CC
CC000 to CC255 Decimal
02H: Input relay
2816 to 3071 MB001760 to MB00191F
M
M2048 to M8191 Decimal
01H/05H/0FH: Coil
8192 to 14335 MB005120 to MB00895F
Table G.8 Valid Range of Data Addresses (MELSEC word device)
Device
Device Range of
ACPU Common
Commands
Decimal/
Hexa-
decimal
Function Code
Valid Range of
Data Addresses
Corresponding Register
Number
TN
TN000 to TN255 Decimal
04H/0AH:
Input register
0 to 255 MW00000 to MW0255
CN
CN000 to CN255 Decimal
04H/0AH:
Input register
256 to 511 MW00256 to MW00511
D
D0000 to D1023 Decimal
03H/06H/09H/0BH/
0EH/10H:
Holding register
0 to 1023 MW00000 to MW01023
D
(special)
D9000 to D9255 Decimal
03H/06H/09H/0BH/
0EH/10H:
Holding register
1024 to 1279 MW01024 to MW01279
W
W0000 to W03FF Hexadecimal
03H/06H/09H/0BH/
0EH/10H:
Holding register
1280 to 2303 MW01280 to MW02303
R
R00
00 to R8191 Decimal
03H/0
6H/09H/0BH/
0EH/10H:
Holding register
2304 to 10495 MW02304 to MW10495
D
D1024 to D6143 Decimal
03H/06H/09H/0BH/
0EH/10H:
Holding register
10496 to 15615 MW10496 to MW15615