2.2  Basic Module
2.2.4  218IFA Module (Ethernet)
2-28
In addition, click the Default Button to set the default values for data code type, local I/O register setting, read/write 
size, and node read/write register setting according to the selected communication protocol type. 
The following table provides these default values.
Communication 
Protocol Type
Default
Data Code 
Type
Local Input/Output Register Setting Read/Write Size
Node Read/Write Register 
Setting
Extended 
MEMOBUS
BIN
IW
 to IW+ 3 (input)
OW
+ 4 to OW+7 
(output)
4 (read)
4 (write)
MW0000 to MW0003 (read)
MW0004 to MW0007 (write)
MEMOBUS RTU
Same as above Same as above Same as above
MELSEC BIN
Same as above Same as above
D0000 to D0003 (read)
D0004 to D0007 (write)
MODBUS/TCP BIN
Same as above Same as above
4X00001 to 4X0004 (read)
4X00005 to 4X0008 (write)