16-7
IM 05P02C41-01EN
Troubleshooting, Maintenance, and Inspections
16
Errors during operation (Input/output Action)
Error
description
PVinput,RSP

input,
andaux.analoginput
Ladder
calcula-
tion
Control
compu-
tation
Control output
Retrans-
mission
output
Alarm
action
Analog out-
put (control
output,
retrans-
mission
output)
V
oltage
pulse out-
put (control
output)
Relayout-
put (control
output,
position
proportion-
al output)
Feedback
input
(for
Position
proportion-
al
type)
Contact
input
Contact
(alarm)
output
Commu-
nication
Burnout error when
RSP input is used for
control (Loop 1)
Depends on the setting
of the parameter BSL
of the analog terminal
connected to the RSP
where the error occurs.
Upscale: 105%
Downscale: -5%
Normal
action
Normal
action
When in AUTO and
RUN modes: Error
preset output
When in MAN
mode: MAN output
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Feedback input
resistor/current burnout
Normal action
Normal
action
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
-
Position
proportional
output: OFF
105%
Normal
action
Normal
action
Normal
action
Ladder calculation
overow
Normal action
Undened
(calculation
with max.
value)
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Load factor is over
100%
Normal action
Does
not work
according to
the control
perio
d.
Does
not work
according
to the
control
perio
d.
Does not work
according to the
control perio
d.
Does
not work
according
to the
control
perio
d.
Does
not work
according
to the
control
period.
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
The
response
from the
main unit
slows.
Load factor is over
200%. (Forced
termination)
Normal action
Forced end
at 200%
Does
not work
according
to the
control
perio
d.
Does not work
according to the
control perio
d.
Does
not work
according
to the
control
perio
d.
Does
not work
according
to the
control
period.
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Ladder program error Normal action
Undened
(Stopped
at the error
detection)
Normal
action
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
Normal
action
16.1Troubleshooting

Table of Contents

Other manuals for YOKOGAWA UP55A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP55A and is the answer not in the manual?

YOKOGAWA UP55A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP55A
CategoryController
LanguageEnglish

Related product manuals