18-50
IM 05P02C41-01EN
SystemSettingMenu(Menu:SYS)
Parameter
symbol
Name
Display
level
Settingrange Initialvalue
R.MD Restart mode STD
CONT: Continue action set before
power failure.
MAN: Start from MAN.
RESET: Start from AUTO and
RESET. The preset output value
is outputted.
* Set how the controller should
recover from a power failure of
5 seconds or more.
CONT
R.TM Restart timer STD
0 to 10 s
* Set time between power on and
the instant where controller
starts computation.
0
EPO
Input error preset
output
STD
0: Preset output
1: 0% output
2: 100% output
* Set preset output value when
the input burnout or ADC
error occurs. Manual output
isprioritizedwhentheinput
burnout occurs in MAN.
0
C.GRN
Response as
GREEN Series
PRO
OFF: Works as UP55A in
communication of device
information response or
broadcasting.
ON: Works as GREEN Series
in communication of device
information response or
broadcasting.
OFF
FREQ Power frequency EASY AUTO,60:60Hz,50:50Hz AUTO
QSM Quick setting mode EASY
OFF: Disable
ON: Enable
ON
LANG
Guide display
language
EASY
ENG: English
FRA: French
GER: German
SPA: Spanish
Depends on
the Model and
SufxCodes
PASS Password setting EASY 0 (No password) to 65535 0
SMEC
Sampling period
error counter
PRO 0 to 65535 (display only)
0 when power
is turned on.
18.2ListofParameters

Table of Contents

Other manuals for YOKOGAWA UP55A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP55A and is the answer not in the manual?

YOKOGAWA UP55A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP55A
CategoryController
LanguageEnglish

Related product manuals