EasyManua.ls Logo

ABB RED650 - Page 105

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start L1
Start L3
Start L2
St L1 IdMinHigh
St L3 IdMinHigh
St L2 IdMinHigh
Diff curr L1 2
nd
harm
Diff curr L3 2
nd
harm
Diff curr L2 2
nd
harm
Diff curr L3 5
th
harm
Diff curr L2 5
th
harm
Diff curr L1 5
th
harm
Line energizing
AND
AND
AND
CrossBlockEn
External fault
Internal fault
OR
tIdMinHigh
t
OR
OR
OR
OR
OR
OR
Trip unrestrained L3
Trip unrestrained L1
Trip unrestrained L2
OR
OR
OR
OR
OR
AND
AND
IEC05000295-3-en.vsd
TRIP
TRL1
TRL2
TRL3
OR
OR
OR
OR
OR
OR
AND
AND
AND
AND
AND
AND
AND
NegSeqDiffEn
IEC05000295 V3 EN-US
Figure 36: Simplified block diagram
Remembering that current values plotted above the characteristic formed by IdMin
and the dual slope in Figure 35 are said to give a start, the output logic can be
summarized as follows:
A start in one phase, gives a trip under the condition that the content of the 2
nd
and the 5
th
harmonic is below the set level for these harmonics in the phase
with start, if CrossBlockEn = OFF. If CrossBlockEn = ON, then all phases
with their start signals set, must be free of their respective harmonic block
signals; otherwise no trip command is issued. Otherwise it is blocked as long
1MRK 505 394-UEN A Section 6
Differential protection
Line differential protection RED650 2.2 IEC 99
Technical manual