Figure 209: Guard signal logic with unblocking scheme
The unblocking function can be set in three operation modes (setting Unblock):
Off: The unblocking function is out of operation
No restart: Communication failure shorter than
tSecurity
will be ignored
If CRG disappears, a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)
Restart Communication failure shorter than
tSecurity
will be ignored
It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be recurrent
signaling
13.4.7 Technical data
M16049-1 v10
Table 243: ECPSCH technical data
Function
Range or value Accuracy
Scheme type Permissive Underreaching
Permissive Overreaching
Blocking
-
Communication scheme
coordination time
(0.000-60.000) s ±0.2% or ±20 ms whichever
is greater
13.5 Current reversal and weak-end infeed logic for
residual overcurrent protection ECRWPSCH
IP14365-1 v4
13.5.1 Identification
M14883-1 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for residual overcurrent protection
ECRWPSCH - 85
1MRK 505 394-UEN A Section 13
Scheme communication
Line differential protection RED650 2.2 IEC 423
Technical manual