15.11.5 Settings
PID-6998-SETTINGS v1
Table 426: TEILGAPC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
tAlarm 1.0 - 99999.9 Hour 0.1 90000.0 Time limit for alarm supervision
tWarning 1.0 - 99999.9 Hour 0.1 50000.0 Time limit for warning supervision
tAddToTime 0.0 - 99999.9 Hour 0.1 0.0 Time to add to the accumulation
15.11.6 Operation principle
GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3
Figure 300 describes the simplified logic of the function.
Time Accumulation
Transgression Supervision
Plus Retain
BLOCK
ACC_HOUR
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC15000322.vsd
Loop Delay
Loop Delay
tWarning
ACC_DAY
ADDTIME
tAddToTime
IEC15000322 V1 EN-US
Figure 300: TEILGAPC Simplified logic
TEILGAPC main functionalities
IN: Accumulation of the elapsed time when input IN is high
1MRK 505 394-UEN A Section 15
Monitoring
Line differential protection RED650 2.2 IEC 605
Technical manual