ABB RED650 - GOOSE Function Block to Receive a Measurand Value GOOSEMVRCV; Identification; Functionality

ABB RED650
926 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data Value Data Valid Comm Valid Test
Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Freeze 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1
Receiver in block Freeze 0 1 0
Receiver in block and communication
error
Freeze 0 0 0
Receiver in test mode and incoming
data with q= Normal
Updated 1 1 0
Receiver in test mode and incoming
data with q= Test
Updated 1 1 1
Communication Error Freeze 0 0 0
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if
easy GOOSE engineering is enabled) to receive the integer values.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
18.4.9 GOOSE function block to receive a measurand value
GOOSEMVRCV
18.4.9.1 Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV - -
18.4.9.2 Functionality
GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3
GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via
GOOSE.
1MRK 505 394-UEN A Section 18
Station communication
Line differential protection RED650 2.2 IEC 651
Technical manual