18.4.10.2 Functionality
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3
GOOSESPRCV is used to receive a single point value using IEC 61850 protocol
via GOOSE.
18.4.10.3 Function block
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
IEC10000248-2-en.vsd
GOOSESPRCV
BLOCK
^SRCSPOUT
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248 V2 EN-US
Figure 323: GOOSESPRCV function block
18.4.10.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the Engineering Manual.
PID-6832-INPUTSIGNALS v3
Table 473: GOOSESPRCV Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCSPOUT BOOLEAN 0 Source to single point output
PID-6832-OUTPUTSIGNALS v3
Table 474: GOOSESPRCV Output signals
Name
Type Description
SPOUT BOOLEAN Single point output
DATAVALID BOOLEAN Data valid for single point output
COMMVALID BOOLEAN Communication valid for single point output
TEST BOOLEAN Test output
18.4.10.5 Settings
PID-6832-SETTINGS v3
Table 475: GOOSESPRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On