15.9.3 Function block
M16684-3 v6
LMBRFLO
PHSELL1*
PHSELL2*
PHSELL3*
CALCDIST*
CALCMADE
FLT_X
BCD_80
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
IEC05000679-4-en.vsd
IEC05000679 V4 EN-US
Figure 292: FLO function block
15.9.4 Signals
PID-3906-INPUTSIGNALS v1
Table 412: LMBRFLO Input signals
Name
Type Default Description
PHSELL1 BOOLEAN 0 Phase selecton L1
PHSELL2 BOOLEAN 0 Phase selecton L2
PHSELL3 BOOLEAN 0 Phase selecton L3
CALCDIST BOOLEAN 0 Do calculate fault distance (release)
PID-3906-OUTPUTSIGNALS v1
Table 413: LMBRFLO Output signals
Name
Type Description
CALCMADE BOOLEAN Fault calculation made
FLT_X REAL Reactive distance to fault
BCD_80 BOOLEAN Distance in binary coded data, bit represents 80%
BCD_40 BOOLEAN Distance in binary coded data, bit represents 40%
BCD_20 BOOLEAN Distance in binary coded data, bit represents 20%
BCD_10 BOOLEAN Distance in binary coded data, bit represents 10%
BCD_8 BOOLEAN Distance in binary coded data, bit represents 8%
BCD_4 BOOLEAN Distance in binary coded data, bit represents 4%
BCD_2 BOOLEAN Distance in binary coded data, bit represents 2%
BCD_1 BOOLEAN Distance in binary coded data, bit represents 1%
1MRK 505 394-UEN A Section 15
Monitoring
Line differential protection RED650 2.2 IEC 591
Technical manual