Name Type Default Description
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for
step4
CBPOS BOOLEAN 0 Breaker position
CLOSECB BOOLEAN 0 Breaker close command
OPENCB BOOLEAN 0 Breaker open command
PID-6967-OUTPUTSIGNALS v3
Table 84: EF4PTOC Output signals
Name Type Description
TRIP BOOLEAN General trip signal
TRIN1 BOOLEAN Trip signal from step 1
TRIN2 BOOLEAN Trip signal from step 2
TRIN3 BOOLEAN Trip signal from step 3
TRIN4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from earth fault switch onto fault
function
START BOOLEAN General start signal
STIN1 BOOLEAN Start signal step 1
STIN2 BOOLEAN Start signal step 2
STIN3 BOOLEAN Start signal step 3
STIN4 BOOLEAN Start signal step 4
STSOTF BOOLEAN Start signal from earth fault switch onto fault
function
STFW BOOLEAN Start signal forward direction
STRV BOOLEAN Start signal reverse direction
2NDHARMD BOOLEAN 2nd harmonic block signal
8.4.5 Settings
IP11454-1 v2
PID-6967-SETTINGS v3
Table 85: EF4PTOC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
EnDir Disable
Enable
- - Enable Enabling the Directional calculation
AngleRCA -180 - 180 Deg 1 65 Relay Characteristic Angle (RCA)
polMethod Voltage
Current
Dual
-
- Voltage Type of polarization
UPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization in
% of UBase
Table continues on next page
Section 8 1MRK 505 394-UEN A
Current protection
184 Line differential protection RED650 2.2 IEC
Technical manual