16.2.6 Monitored data
PID-6872-MONITOREDDATA v3
Table 437: ETPMMTR Monitored data
Name
Type Values (Range) Unit Description
EAFACC REAL - MWh Accumulated forward
active energy value
EARACC REAL - MWh Accumulated reverse
active energy value
ERFACC REAL - MVArh Accumulated forward
reactive energy value
ERRACC REAL - MVArh Accumulated reverse
reactive energy value
MAXPAFD REAL - MW Maximum forward active
power demand value for
set interval
MAXPARD
REAL - MW Maximum reverse active
power demand value for
set interval
MAXPRFD
REAL - MVAr Maximum forward
reactive power demand
value for set interval
MAXPRRD
REAL - MVAr Maximum reverse
reactive power demand
value for set interval
16.2.7 Operation principle
GUID-4A46757C-EC5D-4BCE-9D09-C8152B062CE1 v3
The instantaneous output values of active and reactive power from the
Measurements function CVMMXN are used and integrated over a selected time
tEnergy to measure the integrated energy. Figure
304 shows the overall
functionality of the energy calculation and demand handling function ETPMMTR.
1MRK 505 394-UEN A Section 16
Metering
Line differential protection RED650 2.2 IEC 617
Technical manual