EasyManua.ls Logo

ABB RED650 - Page 622

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
tEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value
Table 436: ETPMMTR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
EALim 0.001 -
10000000000.000
MWh 0.001 1000000.000 Active energy limit
ERLim 0.001 -
10000000000.000
MVArh 0.001 1000.000 Reactive energy limit
EnZeroClamp Off
On
- - On Enable of zero point clamping detection
function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active
Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
DirEnergyAct Forward
Reverse
- - Forward Direction of active energy flow Forward/
Reverse
DirEnergyReac Forward
Reverse
- - Forward Direction of reactive energy flow
Forward/Reverse
EAFPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for forward active
energy
EARPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for reverse active
energy
ERFPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for forward reactive
energy
ERRPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for reverse reactive
energy
Section 16 1MRK 505 394-UEN A
Metering
616 Line differential protection RED650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB RED650

Related product manuals