Name Values (Range) Unit Step Default Description
tEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value
Table 436: ETPMMTR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
EALim 0.001 -
10000000000.000
MWh 0.001 1000000.000 Active energy limit
ERLim 0.001 -
10000000000.000
MVArh 0.001 1000.000 Reactive energy limit
EnZeroClamp Off
On
- - On Enable of zero point clamping detection
function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active
Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
DirEnergyAct Forward
Reverse
- - Forward Direction of active energy flow Forward/
Reverse
DirEnergyReac Forward
Reverse
- - Forward Direction of reactive energy flow
Forward/Reverse
EAFPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for forward active
energy
EARPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for reverse active
energy
ERFPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for forward reactive
energy
ERRPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for reverse reactive
energy
Section 16 1MRK 505 394-UEN A
Metering
616 Line differential protection RED650 2.2 IEC
Technical manual