15.7.5 Settings
PID-4144-SETTINGS v6
Table 408: BINSTATREP Non group settings (basic)
Name
Values (Range) Unit Step Default Description
t 0.0 - 60.0 s 0.1 10.0 Time delay of function
15.7.6 Operation principle
GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3
The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or
via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
t t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 290: BINSTATREP logical diagram
15.8 Measured value expander block RANGE_XP
SEMOD52451-1 v2
15.8.1 Identification
SEMOD113212-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block RANGE_XP - -
15.8.2 Functionality
SEMOD52450-4 v7
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) are
provided with measurement supervision functionality. All measured values can be