Name Values (Range) Unit Step Default Description
MaxIN 1 - 99999 A 1 3000 Maximum residual current IN
MaxUL1 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L1
MaxUL2 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L2
MaxUL3 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L3
MaxUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Maximum voltage for phase-phase L1-L2
MaxUN 0.05 - 2000.00 kV 0.05 230.00 Maximum residual voltage UN
MaxP 0.00 - 2000.00 MW 0.05 1200.00 Maximum value for active power
MaxQ 0.00 - 2000.00 MVAr 0.05 1200.00 Maximum value for reactive power
MaxF 15.0 - 66.0 Hz 1.0 51.0 Maximum system frequency
18.8.3 Measurands user defined signals for IEC 60870-5-103
I103MEASUSR
18.8.3.1 Functionality
GUID-FC9ED4BD-F11C-4BDA-8CDB-3ACF00931D3A v1
I103MEASUSR is a function block with user defined input measurands in monitor
direction. These function blocks include the FunctionType parameter for each block
in the private range, and the Information number parameter for each block.
18.8.3.2 Identification
GUID-A9E21066-354B-453D-8D9B-E86EE31CF5F9 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measurands user defined signals for
IEC 60870-5-103
I103MEASUSR - -
18.8.3.3 Function block
GUID-C234101E-F9B9-4DB0-874C-C51BB50588CB v1
IEC10000288-1-en.vsd
I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
IEC10000288 V1 EN-US
Figure 338: I103MEASUSR function block
Section 18 1MRK 505 394-UEN A
Station communication
708 Line differential protection RED650 2.2 IEC
Technical manual