ABB RED650 - Supervision of Analog Inputs; Technical Data; Changelock Function CHNGLCK; Functionality

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Card Name of signal Description Displayed on
local HMI as
Reasons for activation
ADM ADM-Error A/D
Module
Error
status
ADM32
Activated if the module has a hardware
error.
LDCM LDCM-Error Line
Differentia
l
Communi
cation
Module
Error
status
LDCM3nn Activated if the module has a hardware
error.
n = slot number
TRM
TRM-Error Transform
er Module
Error
status
TRM40
20.5.5.2 Supervision of analog inputs
M11401-136 v7
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification.
When the signal is within measurable limits on both channels, a direct comparison
of the two A/D converter channels can be performed. If the validation fails, the
CPU will be informed and an alarm will be given for A/D converter failure.
20.5.6 Technical data
IP10272-1 v2
M11963-1 v5
Table 573: Self supervision with internal event list
Data
Value
Recording manner Continuous, event controlled
List size 40 events, first in-first out
20.6 ChangeLock function CHNGLCK
GUID-E8A1C33A-DD65-42B5-BA13-CFAE40C2C9AD v2
20.6.1 Functionality
GUID-00784FC0-B39D-462D-854B-AAF62626DD0A v3
Change lock function CHNGLCK is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.
The change lock function activation is normally connected to a binary input.
Section 20 1MRK 505 394-UEN A
Security
768 Line differential protection RED650 2.2 IEC
Technical manual

Table of Contents