Figure 389: IRIG-B PC-MIP board with top left ST connector for optical IRIG-B
00X 820 nm multimode fibre optic signal input and lower left BNC
connector for IRIG-B signal input
22.2.13.3 Settings
PID-5187-SETTINGS v5
Table 643: IRIG-B Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SynchType BNC
Opto
- - Opto Type of synchronization
TimeDomain LocalTime
UTC
- - LocalTime Time domain
Encoding IRIG-B
1344
1344TZ
-
- IRIG-B Type of encoding
TimeZoneAs1344 MinusTZ
PlusTZ
- - PlusTZ Time zone as in 1344 standard
22.2.13.4 Technical data
SEMOD141132-1 v1
SEMOD141136-2 v8
Table 644: IRIG-B
Quantity
Rated value
Number of channels IRIG-B 1
Number of optical channels 1
Electrical connector:
Electrical connector IRIG-B BNC
Pulse-width modulated 5 Vpp
Table continues on next page