The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
 
Data Value Data Valid Comm Valid Test
Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Freeze 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1
 
Receiver in block Freeze 0 1 0
Receiver in block and communication
error
Freeze 0 0 0
Receiver in test mode and incoming
data with q= Normal
Updated 1 1 0
Receiver in test mode and incoming
data with q= Test
Updated 1 1 1
Communication Error Freeze 0 0 0
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (in
case easy GOOSE engineering is enabled) to receive the measured
value.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
18.4.10  GOOSE function block to receive a single point value
GOOSESPRCV
18.4.10.1  Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
single point value
GOOSESPRCV - -
1MRK 505 394-UEN A Section 18
Station communication
Line differential protection RED650 2.2 IEC 653
Technical manual