The front port is only intended for PCM600 communication,
maintenance, training and test purposes due to risk of interference
during normal operation.
18.4.2 Communication interfaces and protocols
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v7
Table 453: Supported station communication interfaces and protocols
Protocol Ethernet Serial
100BASE-FX (ST
connector)
Glass fibre (ST
connector)
EIA-485
IEC 61850–8–1 - -
DNP3
IEC 60870-5-103 -
● = Supported
18.4.3 Settings
PID-6702-SETTINGS v3
Table 454: IEC61850-8-1 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
GOOSEPortEd1 AP_FRONT
AP_1
AP_2
AP_3
AP_4
AP_5
AP_6
-
- AP_1 Selection of GOOSE port (only for
IEC61850 Ed1)
ProtocolEdition Ed 1
Ed 2
- - Ed 1 Protocol Edition
RemModControl Off
Maintenance
All levels
-
- Off Remote Mode Control
AllowSimulation No
Yes
- - No Allow simulated GOOSE values or
simulated sampled measurand values
RemSetControlEd2 Disabled
Enabled
- - Disabled Changing settings over 61850 enabled
(only for IEC61850 Ed2)
ResvTmsEd2 1 - 3600 s 1 60 Reservation time (only for IEC61850
Ed2)