EasyManua.ls Logo

ABB RED650 - Technical Data

ABB RED650
926 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
START
ST1L1
ST1L2
ST1L3
TR1L1
TR1L2
TR1L3
ST1
TR1
START
ST2L1
ST2L2
ST2L3
TR2L1
TR2L2
TR2L3
ST2
TR2
S
T
A
R
T
TRIP
Comparator
UL1 > U1>
Comparator
UL2 > U1>
Comparator
UL3 > U1>
MaxVoltSelect
Comparator
UL1 > U2>
Comparator
UL2 > U2>
Comparator
UL3 > U2>
MaxVoltSelect
Start
t1
t1Reset
&
Trip
Output
Logic
Step 1
Start
t2
t2Reset
&
Trip
Output
Logic
Step 2
Phase 3
Phase 2
Phase 1
Phase 3
Phase 2
Phase 1
Time integrator
tIreset2
ResetTypeCrv2
Voltage Phase
Selector
OpMode2
1 out of 3
2 out of 3
3 out of 3
Time integrator
tIreset1
ResetTypeCrv1
Voltage Phase
Selector
OpMode1
1 out of 3
2 out of 3
3 out of 3
UL1
UL2
UL3
TRIP
TRIP
OR
OR
OR
OR
OR
OR
IEC05000013-2-en.vsd
IEC05000013-WMF V2 EN-US
Figure 118: Schematic design of Two step overvoltage protection OV2PTOV
9.2.8 Technical data
IP13013-1 v1
M13304-1 v14
Table 128: OV2PTOV technical data
Function
Range or value Accuracy
Operate voltage, step 1 and 2 (1.0-200.0)% of
UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Absolute hysteresis (0.0–50.0)% of
UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Inverse time characteristics for steps 1
and 2, see table 674
- See table 674
Table continues on next page
1MRK 505 394-UEN A Section 9
Voltage protection
Line differential protection RED650 2.2 IEC 253
Technical manual

Table of Contents

Other manuals for ABB RED650