PID-6914-OUTPUTSIGNALS v3
Table 62: PHPIOC Output signals
Name Type Description
TRIP BOOLEAN Trip signal from any phase
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
8.1.5  Settings
IP11434-1 v2
PID-6914-SETTINGS v3
Table 63: PHPIOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
OpMode 2 out of 3
1 out of 3
- - 1 out of 3 Select operation mode 2-out of 3 / 1-out
of 3
IP>> 5 - 2500 %IB 1 200 Operate phase current level in % of
IBase
Table 64: PHPIOC Group settings (advanced)
Name
Values (Range) Unit Step Default Description
IP>>Min 5 - 2500 %IB 1 5 Minimum used operate phase current
level in % of IBase, if IP>> is less than
IP>>Min then IP>> is set to IP>>Min
IP>>Max
5 - 2500 %IB 1 2500 Maximum used operate phase current
level in % of IBase, if IP>> is greater
than IP>>Max then IP>> is set to
IP>>Max
StValMult
0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level
Table 65: PHPIOC Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
8.1.6  Monitored data
PID-6914-MONITOREDDATA v3
Table 66: PHPIOC Monitored data
Name
Type Values (Range) Unit Description
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3
Section 8 1MRK 505 394-UEN A
Current protection
160 Line differential protection RED650 2.2 IEC
Technical manual