Name Type Description
APP15VAL BOOLEAN Apparatus 15 position is valid
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output
18.4.11.4 Settings
SEMOD173168-1 v2
PID-6831-SETTINGS v3
Table 478: GOOSEINTLKRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
18.4.11.5 Operation principle
GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1
The APPxVAL output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value Data Valid Comm Valid Test
Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1
Receiver in block 0 0 1 0
Receiver in block and
communication error
0 0 0 0
Receiver in test mode and incoming
data with q= Normal
Updated 1 1 0
Receiver in test mode and incoming
data with q= Test
Updated 1 1 1
Communication Error 0 0 0 0
At least one of the inputs of this GOOSE block must be linked
either in SMT by means of a cross or in ACT by means of a
GOOSE connection (if easy GOOSE engineering is enabled) to
receive any data. Only those outputs whose source input is linked/
connected will be updated.
1MRK 505 394-UEN A Section 18
Station communication
Line differential protection RED650 2.2 IEC 659
Technical manual