• Possibilities for blocking and reset
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time
15.11.3  Function block
GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1
TEILGAPC
BLOCK
IN
ADDTIME
RESET
ALARM
WARNING
OVERFLOW
ACC_HOUR
ACC_DAY
IEC15000323.vsdx
IEC15000323 V1 EN-US
Figure 299: TEILGAPC function block
15.11.4  Signals
PID-6998-INPUTSIGNALS v1
Table 424: TEILGAPC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Freeze the accumulation and block the outputs
IN BOOLEAN 0 The input signal that is used to measure the
elapsed time, when its value is high
ADDTIME BOOLEAN 0 Add time to the accumulation
RESET BOOLEAN 0 Reset accumulated time
PID-6998-OUTPUTSIGNALS v1
Table 425: TEILGAPC Output signals
Name
Type Description
ALARM BOOLEAN Indicator that accumulated time has reached
alarm limit
WARNING BOOLEAN Indicator that accumulated time has reached
warning limit
OVERFLOW BOOLEAN Indicator that accumulated time has reached
overflow limit
ACC_HOUR REAL Accumulated time in hours
ACC_DAY REAL Accumulated time in days
Section 15 1MRK 505 394-UEN A
Monitoring
604 Line differential protection RED650 2.2 IEC
Technical manual