18.5.4 Settings
SEMOD166625-1 v2
PID-6850-SETTINGS v3
Table 486: MU1_HW Non group settings (basic)
Name
Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTStarPoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
18.5.5 Monitored data
PID-6850-MONITOREDDATA v3
Table 487: MU1_HW Monitored data
Name Type Values (Range) Unit Description
MUDATA BOOLEAN 0=Ok
1=Error
- Fatal error, data not
received, transmission
errors, time-sync issues
or inconsistent sample
rate
SYNCH
BOOLEAN 0=Ok
1=Error
- High when IED clock is
not within configured
accuracy or time domain
SMPLLOST
BOOLEAN 1=Yes
0=No
- Fatal error or recovery
state after fatal error.
High if any subscribed
channel has bad quality
or TEST while IED not in
test mode.
MUSYNCH
BOOLEAN 0=Ok
1=Error
- MU not synced or MU
clock not synced to
same clock as IED
TESTMODE
BOOLEAN 1=Yes
0=No
- Quality of one or more
subscribed analogue
channels is TEST
SIMMODE
BOOLEAN 1=Yes
0=No
- MU delivers simulated
data accepted by IED
BadReference BOOLEAN 1=Yes
0=No
- BadReference indication
output for I1
Derived BOOLEAN 1=Yes
0=No
- Derived indication output
for I1
Failure BOOLEAN 1=Yes
0=No
- Failure indication output
for I1
Inaccurate BOOLEAN 1=Yes
0=No
- Inaccurate indication
output for I1
Inconsistent BOOLEAN 1=Yes
0=No
- Inconsistent indication
output for I1
Table continues on next page
Section 18 1MRK 505 394-UEN A
Station communication
668 Line differential protection RED650 2.2 IEC
Technical manual