Name Values (Range) Unit Step Default Description
ZoneSeqCoord Off
On
- - Off Coordination of down stream devices to
local protection unit’s AR
tSuccessful 0.000 - 60.000 s 0.001 1.000 Delay time before indicating successful
reclosing
tSlaveDeadTime 0.100 - 60.000 s 0.001 0.400 Wait time for the slave to close when
WAIT input has reset
12.2.6 Operation principle
12.2.6.1 Terminology explanation
GUID-EA0760DF-8F0B-4146-8A42-3F20E75E1053 v1
Before describing the auto reclosing function it is first necessary to define the
following terminology:
a shot is an attempt from the function to close a circuit breaker
multi-shot is where more than one shot is attempted
dead time is the time between a start of the function and the attempt to close
the circuit breaker
reclaim time is the time from the circuit breaker closing command till the
reset of the function, should the auto reclosing attempt be successful and no
new start is received
high-speed shot is generally used for an application where the dead time is
less than 1 second and synchrocheck is not required
delayed auto reclosing is generally regarded as an application where the dead
time is greater than 1 second and where typically synchrocheck is required
sequence is the auto reclosing cycle beginning with start and ending with
successful, unsuccessful or aborted reclosing as a result
status is the state which the auto reclosing function have reached in the
sequence
12.2.6.2 Status descriptions
GUID-AFC069D6-ADA5-4D97-9699-8C9F058458EB v1
The auto reclosing function can be in one of the following five statuses:
“Inactive”
GUID-BF80C969-FCBE-4CAB-BF71-9590A2DB433C v1
The auto recloser is in “inactive” status when the following conditions are fulfilled:
the auto recloser is set to On and
either the circuit breaker is not closed
or the circuit breaker is not ready
The function will not react on any start from protection trips while in
“inactive” status and no automatic reclosing is possible.